What circuit breakers are HACR labeled? A complete list.

Issue:
Which circuit breakers are HACR labeled?  A complete list.

Product Line:
All molded case circuit breakers

Environment:
Electrical distribution equipment

Cause:
Customer specifications

Resolution:
Square D/Schneider circuit breakers with HACR labeling include: 
HOM HOMT 
QO QOB QOU 
FA, FH
BD BG BJ BK
HD, HG, HJ, HL, HR
JD, JG, JJ, JL, JR
DG, DJ, DL
LA, LH Q4
LD, LG, LJ, LL
MA, MH
MG, MJ
PG, PJ, PL
RG, RJ, RL
ED, EG, EJ
FD, FG, FJ

Please see link below to data bulletin 0600DB0102 for a complete list of HACR labeled breakers:
http://static.schneider-electric.us/docs/Circuit%20Protection/Molded%20Case%20Circuit%20Breakers/0600DB0102.pdf

Section 7.8 of the 11th edition of UL 489 granted HACR listing to all UL 489 Listed circuit breakers. There is no longer a requirement for special testing. Circuit breakers with UL 489 listing are suitable for group motor applications requiring HACR designation.
 