Technical FAQs

Ask a Question

Video: How to increase the starting torque on the ATS22?

Issue:
Not enough power to get the motor moving from a start position

Product line:  
Altistart 22, ATS22

Environment:  
All models, all serial numbers

Cause:
The default settings in the ATS22 cannot produce enough torque to ramp up the softstart, which could lead to overcurrent, overload or execessive starting time faults.

Resolution:
Increasing the parameters below can aid in providing more breakaway torque to get the motor moving and up to speed.

SET Menu
Parameter T90 – Initial Voltage.  This value is adjustable from 10% to 50% of the full voltage, in increments of 5%.  Factory setting is 30%. 
Paramter ILt - Current limit.  This is the maximum current allowed during the startup.  It is adjustable up to 700% of the Motor Rated Current (In parameter).  The maximum value is 350% of the Softstart rated current (IcL parameter).  Factory setting is 350%.

ADJ Menu (To access the ADJ menu, LAC parameter under the SET menu must be set to "on")
Parameter bSt – Boost Time.  This provides an 80% pulse of the Line voltage (UIn parameter) for 0.0 to 1.0 seconds.  Factory setting is 0.0. 

 
Was this helpful?
What can we do to improve the information ?