Technical FAQs

Ask a Question

What can cause an error code EPHO on the ATV21 and ATV212 drives?

EPHO or output phase loss fault
Product Line:
ATV212, ATV21
All models and serial numbers
Motor may not be connected.
Check that the motor is connected to the drive. If the unit has a bypass option you will have to disable the output phase loss protection by setting F605 to 0.
Was this helpful?
What can we do to improve the information ?