Technical FAQs

Ask a Question

How is the ATV312 default display changed to show a different monitored parameter?

Issue:
How is the ATV312 default display changed to show a different monitored parameter?

Product Line:
ATV312  ATV31

Environment:
All

Cause:
Preference is to normally display a parameter such as motor current or motor torque, not the factory default of output frequency.

Resolution:
Go to SUP menu and display the parameter to be used as a default display ( eg. LCr or Otr ).  Press ENT once to show the current value of that parameter.  Then press and hold ENT for about 2 seconds and the display will flash, indicating the process is complete.
Was this helpful?
What can we do to improve the information ?