Technical FAQs

Ask a Question

Are there any branch breaker restrictions in a 400a Nema 3R NF panel ?

Issue:
Branch breakers

Product Line:
Panelboards

Environment:
NF

Cause:
Selection

Resolution:
The largest true branch is 125a and sub-feed breaker is 150a . Also 5 branches at 70a or more is a limit .

Was this helpful?
What can we do to improve the information ?