 Issue:
 How to read the current fault status of the VFD?

Product line:  
Altivar 61/71/32/312

Environment:  
All range All serial number   

Cause:
What is the difference between LFT and ERRD on the ATV61 and ATV71?
Resolution:
The difference between Last Fault (LFT), address 7121 and Drive Fault (Errd), address 8606, is LFT is the last Fault and Errd is the current fault. The last fault is stored in registers on the VFD, therefore when reading address 7121, you will be reading from a register with a stored value. If the current fault status is desired then you should read address 8606, the VFD current fault status. 