Can SoMove transfer the configuration from one drive to another of the same model number but different firmware levels?

Transfer programming from one drive to another using SoMove Lite.

Product Line:
Altivar Variable Frequency Drives

All models compatible with SoMove Lite.


It is possible to transfer a configuration from one drive to another drive of the same rating and different firmware versions.  However there may be problems if going from a new firmware level to an older firmware level if the new has additional parameters or if the new firmware include a physical hardware update like a new micro processor.