How much space is required to add a PM 800 Series Power Meter in a NQ Panelboard enclosure ?

Issue:
How much space is required to add a PM 800 Series Power Meter in a NQ Panelboard enclosure ?
 

Product Line:
NQ Panelboards and Powerlogic Power Meters
 

Environment:
The need to monitor the Energy used in a Panelboard requires a meter
 

Cause:
The NQ Panelboard enclosure needs extra inches of mounting space, from the Facory, to accomodate the Power Meter enclosure


Resolution:
The enclosure will be extended 7" in Width and 6" in Height  to accomodate the Meter 














 