Can a QOB3125VH be used on a 240v grounded B phase application ?

Issue:
Can a QOB3125VH be used on a 240v grounded B phase application ?

Product Line:
NQ Panelboards sold and supported in the USA

Environment:
NQ panelboard application 

Cause:
Application 

Resolution:
Yes and it  takes six pole spaces and limits anything mounted opposite to 20A