How do I send a fault reset over Modbus to the ATS48?

The ATS48 needs to have a fault reset sent over Modbus.

Product Line:
Altistart 48

All models and serial numbers.


Fault reset is performed when bit 7 of command word 400 transitions from 0 to 1.  Write decimal 128 to register 400.  If there is an offset then write decimal 128 to register 401.  Once the reset has been performed write a decimal 0 to the register to reset bit 7 to 0 to allow transition when the next reset is performed. 