How does the Repeat Cycle work for a 9050JCK70V20 Timing relay?

 

Issue: 
How does the Repeat Cycle work for a 9050JCK70V20 Timing relay?
 

Product Line:
9050JCK timers

Environment:
The 9050JCK70V20 multi function Timer has a different function that standard 9070JCK5* Repeat Cycle Timers

Cause:
Clarification is needed, verifying how the On and Off times for the 9050JCK70 are setup

Resolution:
The 9050JCK70  Repeat Cycle timing Mode works when control power is applied to the coil. The Off time begins. At the end of the Off time , the output contacts energize and the On Time begins. At the end of the On Time, contacts de-energize and Off Time beigins. This sequence conitues until control power is removed from the coil. The 905JCK70 Timer can only have the same time intervals of Off and On times.