How to reset the ATV61/71 VFD parameters to factory setting?

Issue:
How to reset the ATV61/71 VFD parameters to factory setting?

Product Line:
ATV61/71

Environment:
All range, All serial number

Cause:
Need to reset the ATV61/71 VFD parameters to factory setting?

Resolution:
To factory reset the VFD customer must go to the Drive menu
1.12 Factory Setting press enter
- Parameter group list – Select All press enter
- Then press Esc
- Goto Factory setting press enter
- Please check that wiring is ok press enter


Factory reset is done.

 

 

 

 