What causes a rough or an unsmooth acceleration ramp?

Issue:
The acceleration ramp is not smooth

Product Line:
Altistart 48

Environment:
All models and serial numbers

Cause:
The soft start is in torque control

Resolution:
Turn torque control off.  From the DrC menu change parameter CLP to off.