RJ or RL Powerpact breaker is not passing primary injection testing for ground fault. Just installed a new trip unit.

Issue:
RJ or RL Powerpact breaker is not passing primary injection testing for ground fault.  Just installed a new trip unit.

Product Line:
Powerpact RJ or RL

Environment:
New trip unit on older breaker  with date code of 09011 and older.

Cause:
New trip unit not compatible with older breaker

Resolution:
Do NOT install this trip unit in Compact NS1600b–3200 H Interruption
Rating or PowerPact RJ/RL Circuit Breakers with date code of 09011 or
earlier (A, Figure 1).  See attached Micrologic Special Instructions 48049-160-01.

Install older trip unit or replace breaker to resolve.