Technical FAQs

Ask a Question

What causes an OLF on the ATV12? (also ATV312, ATV32, ATV61, ATV71)

Getting an OLF fault on a  ATV12 drive.

Product Line:
Altivar ATV12


Motor is pulling to much current

Motor overload fault (OLF) is triggered by the motor pulling current above the ItH (Motor Them Current) that is programmed into the drive.  The further above the ItH setting the current is, the less time it will take to trip on OLF. 
Check motor  load. Check motor nameplate settings in the drive. Also check current limitation settings.  Verify the motor current is balanced in all three legs, and not exceeding the motor FLA.   Check that the motor thermal current setting (ITH) is programmed according to motor name plate.
Note that by default the ATV12 drive does not store the thermal state of the motor when power is removed from the drive, so this fault could be reset by a power cycle without  waiting for the motor to cool. 
It is recommended to change the Motor thermal state memo from NO to YES.  This means the OLF fault can not be cleared by a power cycle.  Instead power needs to remain on the drive until the calculated thermal state of the motor has dropped to an acceptable level.
The Motor thermal state is displayed in the Monitoring menu, parameter tHr.   The drive will trip when the tHr parameter reaches 118%.  It will not allow a reset until the tHr drops below 100%.

Was this helpful?
What can we do to improve the information ?