Is a neutral CT needed on a system with just 3 wire downstream loads?

Does a Micrologic circuit breaker with an LSIG trip unit require a neutral CT if it feeds just 3-wire downstream loads (no neutral)?

Product Line:
Molded Case Breakers:  

Powerpact H, J, L P, R and Masterpact NW and NT with Micrologic trip units

Installing and Wiring

No, in this case the neutral would have no place to install and no function. For Masterpact and Powerpact breakers, you would just need to connect a jumper between T1 and T2 on the trip unit.