Why does the ATV212 display a flashing StOP when changing from utility to generator power?

Drive is alarming on Stop Supply whenever there is a power transfer.

Product Line:
ATV21, ATV212

All models and serial numbers

Momentary power loss removes output power to motor.

When F302, supply loss behavior, is enabled, a brief loss of input power will cause the drive to remove power from the motor and display the flashing StOP alarm.  To restart operation, remove and reapply a new run command signal.  To disable this function and attempt to ride through the momentary loss of power, set F302 back to the factory default of 0.