Issue:
Product Design Features

Product Line:
Heavy Duty Safety Switch

Environment:
Class J Fuse conversion

Cause:
Application

Resolution:
Provisions for installing Class J fuses are included in 30A - 400A, 600V and 100A - 400A 240V,  fusible Heavy Duty safety switches. Conversion to Class J fuse spacing requires relocating the load side fuse base assembly (or assemblies where applicable) from the standard Class H or R fuse location to an alternate position as marked in the switch enclosure. Switches rated 600A, 240V or 600V, require the addition of an adapter kit, catalog number H600J.
PLEASE MAKE SURE NEVER TO WORK ON ENERGIZED EQUIPMENT.