Energy Meter shows "Phase Loss" Alarm

Issue
Energy meter shows “Phase Loss” alarm on front display. User is using EMB3164 (3 phase, 4 wire) energy meter to monitor 1phase 2 wire load. 

Product Line
Energy meter (EMB and EME series)

Environment
Installing/wiring energy meter

Cause
Users have wired their three phase energy meter for a single phase load and there is a phase loss indication for B phase.
The EME3xxx series meters are designed and calibrated to accept three current inputs and three voltage inputs.
If you install an EME3xxx on a system that has one or two current/voltage phases, the Energy Meter will report a phase loss because it is not monitoring an input from the third phase. This is a misapplication of the EME3xxx Energy Meter series.

Resolution
It’s very important to know the model number of your Energy meter.  
For example, users see “Phase Loss” error when they use EMB2043 (1 phase, 3 wire) with 1 phase, 2 wire application.

As a result, it’s very important for users to know their application and use appropriate meter that meets their system type.  Please review the tables below for selecting correct meter.

(NOTE: Users can not use 3 phase meter (EMx3xxx) to monitor single phase application)  

Basic 120/240 Volt 208 Wye

EMB1010 Basic 100A 1 Phase, 2 wire installation 1 CT
EMB1021 Basic 200A 1 Phase, 2 wire installation 1 CT
EMB1032 Basic 300A 1 Phase, 2 wire installation 1 CT
EMB2010 Basic 100A 1 Phase, 3 wire installation 2 CTs
EMB2021 Basic 200A 1 Phase, 3 wire installation 2 CTs
EMB2032 Basic 300A 1 Phase, 3 wire installation 2 CTs
EMB2043 Basic 400A 1 Phase, 3 wire installation 2 CTs
EMB2083 Basic 800A 1 Phase, 3 wire installation 2 CTs
EMB3010 Basic 100A 3 Phase, 4 wire installation 3 CTs
EMB3021 Basic 200A 3 Phase, 4 wire installation 3 CTs
EMB3032 Basic 300A 3 Phase, 4 wire installation 3 CTs
EMB3043 Basic 400A 3 Phase, 4 wire installation 3 CTs
EMB3083 Basic 800A 3 Phase, 4 wire installation 3 CTs
EMB3084 Basic 800A 3 Phase, 4 wire installation 3 CTs
EMB3164 Basic 1600A 3 Phase, 4 wire installation 3 CTs


Extended Range 120/480 Volt Wye
 

EME1010 Basic 100A 1 Phase, 2 wire installation 1 CT
EME1021 Basic 200A 1 Phase, 2 wire installation 1 CT
EME1032 Basic 300A 1 Phase, 2 wire installation 1 CT
EME2010 Basic 100A 1 Phase, 3 wire installation 2 CTs
EME2021 Basic 200A 1 Phase, 3 wire installation 2 CTs
EME2032 Basic 300A 1 Phase, 3 wire installation 2 CTs
EME2043 Basic 400A 1 Phase, 3 wire installation 2 CTs
EME2083 Basic 800A 1 Phase, 3 wire installation 2 CTs
EME3010 Basic 100A 3 Phase, 4 wire installation 3 CTs
EME3021 Basic 200A 3 Phase, 4 wire installation 3 CTs
EME3032 Basic 300A 3 Phase, 4 wire installation 3 CTs
EME3043 Basic 400A 3 Phase, 4 wire installation 3 CTs
EME3083 Basic 800A 3 Phase, 4 wire installation 3 CTs
EME3084 Basic 800A 3 Phase, 4 wire installation 3 CTs
EME3164 Basic 1600A 3 Phase, 4 wire installation 3 CTs