How can you break down the ETA status word 3201 on the ATV61 and ATV71 drives?

Needs to know what the 16 bit breakdown is for the ETA status word.

Product Line:
Alitvar ATV61 and ATV71

With Profibus option card

Needs to know the bit breakdown for the ETA status word.

ETA status word for Word 3201
bit 0= Reserved
bit 1= Ready
bit 2= Running
bit 3= Fault
bit 4= Power section line supply present
bit 5= Reserved
bit 6= Reserved
bit 7= Alarm
bit 8= Reserved
bit 9= Command or Ref via network
bit 10= Referenced reached
bit 11= Reference outside of limit
bit 12= Reserved
bit 13= Reserved
bit 14= Stop via Keypad stop button
bit 15= Direction of motor  1=reverse 0=forward.