Is the PJA I-Line panelboard mount breaker available as 100%?

Issue:
PJA availability in 100% rating.

Product Line:
Powerpact P Frame Circuit Breakers

Enviroment:
Available only up to 800A maximum.

Cause:
There is a demand for 100% rated 1000A and 1200A breakers in panel boards.

Resolution:
The PJA I-Line circuit breaker is available with 100% rating up to 800A only.  For 100% rated 1000A and 1200A breakers, it is necessary to use the R frame Powerpact breaker.

 