Powerlink G3 Modbus Direct Breaker Control ASCII Examples

Issue:
Modbus direct breaker control integration.

Product Line:
Powerlink G3 Master panel direct breaker control Modbus Example

Environment:
Modbus

Cause:
ALL ASCII strings are to be followed by <CR><LF> per Modbus standard. The ":" start character is shown in the string.

Resolution:
See attached reference guide for Modbus example:
 
Bus_Breaker #
Trim # (Reference)
ON String
OFF String
0L_1
1
:01050BB7FF0039
:01050BB7000038