What is the proper application and wire range of PDC lugs?

How many wires of what size and range will Power Distribution Connectors accept, and what other criteria apply to application of these lugs?

Product Line:
Legacy and Powerpact MCCBs

Industrial control panels and OEM equipment

These special purpose lugs will accept multiple wires of different sizes and the number and size of wires are selection criteria


Power Distribution Lugs are special purpose and are not rated or certified for use in branch or feeder circuit applications.

General application information for these special purpose lugs:
• Only for use on the OFF (O) end circuit breaker and only when the OFF (O) end is the load end.
• For use in UL 508 Industrial Control Equipment Standard Applications.
• For use in UL 1995/CSA C22.2 No. 236 Heating and Cooling Equipment Standard Applications.
• For copper wire only.

For lug installation data, including wire size and number and torques, see table 2 in attached instruction bulletin 48040-929-04.