Is it possible to power the ATV61 or ATV71 drive with an external +24V power supply?

Issue:
Is it possible to power the ATV61 or ATV71 drive with an external +24V power supply?

Product Line:
ATV61, ATV71

Environment:
All

Cause:
Fault code information is needed with no line voltage applied to the drive.

Resolution: 
Yes, an external +24Vdc can be connected between P24 and 0V terminals to supply control voltage. This will allow you to power the control board and HMI to read drive information.