ATV212: Can the keypad on the front of the drive be locked or password protected?

Issue:
ATV212: Can the keypad on the front of the drive be locked or password protected?

Product Line: 
Altivar212  ATV212

Environment: 
All

Cause: 
Disable HMI programming  

Resolution: 
F700 parameter lock , can be set to 1, which will lock all parameters except F700.