How to adjust the torque boost or voltage boost on the ATS48 soft starter

Issue:
How do you adjust the toque boost or voltage boost on the ATS48 soft starter?

Product Line:
Altistart ATS48

Environment:
All

Cause:
factory default starting motor torque is 20% and voltage boost is set to off.

Resolution:
Set Menu
T90  set to desired torque setting.  Example 100% would mean 100% starting torque at start up.

drC Menu
bSt= set to voltage boost level.