ATV32 Basic Programming

Issue:
ATV32 Basic Programming.

Product Line:
Altivar ATV32

Environment:
All

Cause:
Programming configuration set up

Resolution:
CONF>FULL>SIM Menu set up
bFr= Base motor frequency 60hz
nPr= HP of he motor 10HP
UnS= Rated motor voltage 460vac etc
nCr= Rated motor current 12 amps
FrS= Rated motor frequency 60hz
nSP= Ratd motor speed 1750 rpms
tFr= Max frequency
ItH= Motor thermal current is motor full load amps value
ACC= ramp up time
dEC= ramp down time
LSP= Low speed
HSP= High speed

Programming manual part number  S1A28692