ATS22 how can you reset it back to factory default settings?

ATS22 how can you reset it back to factory default settings?

Product Line:
Altistart 22, ATS22


Resetting current settings back to the orginal factory settings.

Hold the ESC and UP arrows at the same time for 5 seconds, then the display will show the Utility menu - UtIL.
Push the enter button. 
Use the arrow keys to scroll to paramter FCS, (Back to factory settings)
     Push the Enter button. 
Push Enter once and you will get a prompt for "sure".  Push the Enter button again will reset the soft starter back to factory defaults. 