Technical FAQs

Ask a Question

What circuit breaker types will an QMBHW, QMB branch circuit breaker unit accept?

Issue:
What circuit breaker types will an QMBHW, QMB branch circuit breaker unit accept?

Product Line:
QMB panelboard, switchboard with QMB distribution.

Environment:
Products sold and used in the United States.

Cause:
Not all of the PowerPact H frame breakers should be uesd in the QMBHW.  The HJA and HLL types are not listed for use in the QMBHW.

Resolution:
The QMBHW will accept the 15a to 150a HDL and HGL type circuit breakers.
Was this helpful?
What can we do to improve the information ?