Where do I check for a last fault code on an ATV31 and ATV312 drives?

Issue: 
No fault code displayed, after drive reset.

Product Line:
ATV31 and ATV312

Environment:
 All

Cause:  
Would like to know the last drive fault .

Resolution: 
Go to SUP (monitoring menu)  and select  parameter  "LFT" to display the last  drive fault.