Can a GFM150HD, GFM250JD be operated on a 3w system without a neutral, and how is it wired ?

Issue:
Using Ground Fault Module

Product Line:
Ground Fault Equipment

Environment:
3w system

Cause:
Application

Resolution:
Yes it can be operated on a 3W system provided system is grounded.

On this system the neutral CT is not required, therefore leave terminals 5 and 6 open, do not jumper terminals 5 and 6.