Video: How do you wire the ATS22 with S6U suffix for 2 wire control?

Issue:
Wiring the ATS22 with S6U suffix for 2 wire control

Product Line:
Altistart 22, ATS22

Environment:
All of the Altistart 22, ATS22 ending with S6U suffix (120V)

Cause:
Basic wiring examples

Resolution:



The S6U requires constant 120VAC to terminals CL1 (hot) and CL2 (neutral). 

Connect a jumper from Terminal LI1 to LI2.  
Connect a jumper from Terminal CL2 to COM.
Close a dry contact between Terminals CL1 and LI2 for a run forward.  Open this connection for a freewheel stop. 

Reference the User manual # BBV51330 or the Quick Start Annex # S1A14738 for more information.