Is there a manual over ride on the 8903PB panel board lighting contactors?

Issue:
Is there a manual over ride on the 8903PB panel board lighting contactors?   
   
Product Line:
Panel board style lighting contactors      
      
Environment:
8903PB
   
Cause:
Product features
Resolution:
There is a metal piece that is provided in the vertical slot on the front of the contactor. The metal piece has a hole in it.
You can insert an allen wrench to manually open and close the power poles on the contactor.
This will manually override any other control device in the control circuit such as a timer, relay or other controls.  