What does OCA fault mean on the ATV21 and ATV212 drives?

What does the OCA fault mean on the ATV21 or ATV212 drives?

Product line:
Altivar 212, ATV212, S-Flex

All models, all serial numbers.

Overcurrent during start-up or ground fault

Disconnect the motor leads from the drive.  Using a 1000V Megger, check the motor and motor leads for shorts or ground fault.

Try a voltage balance test.  With the motor leads still disconnected, set parameter F605 to 0 (disable Output Phase Failure).  Run the drive at 20Hz, 40Hz and 60Hz.  At each speed measure the line to line output voltages to see if they are balanced.