ATV212 S-Flex Drives: How do I connect to get run status from the drive?

Issue
ATV212 and S-Flex 212 drive run status wiring terminals.
 
Product line:
Altivar ATV212

Environment: 
All models, all serial numbers 

Cause:  
Wiring for drive run status 

Resolution: 

For ATV212 and current S-Flex enclosures: Wire directly to RY and RC for Run status when in AFC. F130 must be programmed to 14: Drive Running.  When the drive run command is received these contacts change states, normally open contacts, close. They will reopen when the run command is removed  or fault stops the drive.    When in Bypass the status is available on terminals 13 and 14.

For S-Flex enclosures 6/2011 and earlier: RYA ( terminal 11) and  RYC (terminal 12) on the drive is programmed for Drive RUN (F130 must be programmed to 14: Drive Running). When the drive run command is received these contacts change states, normally open contacts, close. They will reopen when the run command is removed  or fault stops the drive.  When in Bypass the status is available on terminals 13 and 14.

For S-Flex drives with LON option cards installed, the RY and RC terminals are not available.   Status when running in AFC mode must come from the network
 
 

 

 

 

 

 