How to set up an ATV12 drive so that R1 closes upon motor run status?

Issue:
How to set up an ATV12 drive so that R1 closes upon motor run status?

Product line:
Altivar 12, ATV12
 
Environment:
All models, all serial numbers
 
Resolution:
The Altivar 12 has an NO/NC programmable contact on terminals R1A-R1B-R1C.  (NO is R1A to R1C, NC is R1B to R1C). 

To setup R1 to indicate the drive is running you need to assign this function to the R1 relay.

Go to the following menu:
COnF > FULL > I_O- > r1.  Change this parameter to rUn
When the drive is providing voltage to the motor, the R1A-R1C contact will be closed. 
See User Manual BBV28581 for more details.