Technical FAQs

Ask a Question

E-Flex Altivar 61 How can I invert the mA analog input signal?

Issue:  
How can you invert the mA signal so the drive runs at low speed at 20mA and high speed at 4mA?

Product line:
Altivar ATV61, ATV71
 
Environment:
All models, all serial numbers

Cause:
 Inverting the mA analog input signal

Resolution:
Menu 1.5 AI2 configuration AI2 min set to 20mA and  AI2 max set to 4mA
ATV71_programming_manual ref  
Was this helpful?
What can we do to improve the information ?