What breakers will can be used in a QO2L30S load center?

What breakers will fit in a QO2L30S?

QO2L30S Main Circuit Breaker Load Centers

Indoor only

This question has been raised due to selecting the correct circuit breakers for this load center.

The QO2L30S will accept (1) double pole or (2) single pole QO breakers. It will not accept type QO-EPD, QO-GFI, QO-AFI, QOB, QOT tandem or QO tandem circuit breakers. This is a 2 space/2 circuit panel, accepting full size QO branch circuit breakers only. The 30 ampere panel rating should not be exceeded, or 25 ampere when aluminum feeder wire is used.