What is the minimum meggar reading of bus duct?

ISSUE
 
Customer is testing bus duct with a meggar.
 
 
PRODUCT LINE
 
 Busway or bus duct
 
ENVIRONMENT
 
 Powerbus or I-Line Busway
 
CAUSE
 
 Customer is performing routine maintenance
 
RESOLUTION
 
The minimum Megohm reading for bus duct is 100Megohms divided by the length of run in feet.  100Mohm/feet

 