Issue:
The customer wants a signal from the drive indicating that the motor is running

Product line:
Altivar 212  

Environment:
All models, all serial numbers   

Cause:
None 

Resolution:
Wire to the RYA and RYC relay and program F130 to 14 (drive running).   The relay will close if a run command is issued and there are no faults.