Technical FAQs

Ask a Question

Is it OK to put a disconnect between a VFD drive and the motor?

Issue:
Is it OK to use a motor disconnect on the output of a VFD drive?

Product Line:
All open style and enclosed Altivar drives.

Environment:
All models, All Serial numbers

Cause:
Information not available in existing literature.

Resolution:
A disconnect can be used between the drive and the motor. This is general practice to assure that power does not reach the motor during maintenance and other non-operating times. Note that the disconnect should not be opened or closed while the motor is running. This will damage the output IGBT components of the drive and such damage is not covered under warranty.  Recommend adding a fast acting auxiliary contact on the disconnect that will trigger a freewheel stop on the drive before the main 3 phase contacts open.
 
Was this helpful?
What can we do to improve the information ?