SFLEX, ATV212 - Would like to display percentage instead of frequency on display of the drive.

Issue: Would like to display percentage instead of frequency on display of the drive.
Product line: Altivar 21, Altivar 212, ATV21, ATV212, S-Flex
Environment: All models and all serial numbers.
Cause: The drive originally is setup to output Hz on the main screen.
Resolution: In order to display a percentage value instead of Hz, go into AUF, F--- submenu, and F702. Provide a value of 1.67 to convert 60 Hz to 100 percent.