ATV312 - can he use 0-10 milli amps to control the speed?

Where can you connect a mA signal to the ATV312 drive.

Product line:
Altivar ATV312 

All models, all serial numbers 

This drive uses terminals AI3 and COM for the mA signal.  It can be configured as 0-20mA or 4-20mA. 

Under the I-O_ menu go to CRL3 to adjust the minimum value and CRLH to adjust the maximum value. 