How to set 4-20mA with terminal control as start/stop on ATV312 drive?

Issue:
Speed reference is 4-20mA signal and command start and stop with terminals.

Product Line:
ATV312

Environment:
All models and serial numbers

Cause:

None

Resolution:
Go to menu CtL (Control) - Change parameter FR1 to AI3.  The speed reference default is AI1.  The start/stop command default in 2 wire control between +24 and LI1.