How to set a start/stop on LI1 and a LSP speed on ATV312 drive?

Issue:
Customer wants to use terminal control with start/stop on LI1 and a LSP speed on ATV312 drive?

Product Line:

ATV31 and ATV312
 
Environment:
All models and serial numbers
 
Cause:
None

Resolution:
Enter the motor parameters in the DRC menu (BFR: UNS, FRS: NCR: NSP).
Wire a start/stop contact between LI1 and +24V.  Set low speed in the SET menu with parameter LSP.  Assign the value in frequency. 