Will the ATV212 and ATV312 drives have output phase loss protection?

Looking for protection from the loss of an output phase. 

Product Line:
Altivar 212, Altivar 312

All models, all serial numbers. 

Phase protection

Both the ATV312 and ATV212 have output phase loss protection. 

Output phase protection can be disabled on both of these drives.
For the ATV312 go to FLT > OPL and change from YES to NO to disable phase protection.
For the ATV212, hit Mode until you see AUF, then scroll down to F - - - and hit Enter.  Scroll down to F605 and change to 0 to disable. 