Video: How can you program the ATV212 drive to follow 0-10vdc speed signal on VIA and start/stop via terminal control?

Issue:
How can you program the ATV212 drive to follow 0-10vdc speed signal on VIA and start/stop via terminal control?

Product Line:
Altivar ATV21 and ATV212

Environment:
All

Cause:
Wants to use VIA for 0-10vdc speed control and start stop via 2 wire control thru the terminal inputs.

Resolution:
Switch VIA SW100 setting:  Set the switch on the main circuit board to U for an 0-10vdc input signal on VIA.
Wiring= 0-10vdc signal to VIA and CC    two wire start dry contact is wired between P24 and F.
Programming set FNOD= 1 VIA CNOD= 0 terminal control,  F111= 2  for 2 wire control.
Basic programming
uLu= motor voltage
F415= normal motor current
F417= normal motor RPMs
thr = normal motor current



 