Technical FAQs

Ask a Question

How is the DC injection braking setup on the ATV212 drives?

Program the following:
F250 =  DC braking starting frequency, set to a value > 0  
F251 =  DC braking current  level
F252 =  DC braking time  

Caution:  Prolonged periods of DC injection can damage the motor.


CTA-ID : 2061858
Was this helpful?
What can we do to improve the information ?