How is the ATV212 setup for 2 preset speeds?

Drive is to run at 2 different specific speeds.

Product Line:
Altivar 212 ATV212

All models

Application requirements

The slower speed is assigned to LL and a logic input activates the higher speed which is assigned to Sr1.  
For example, logic input R is assigned F112 = 6.  When R is low, the drive runs at speed LL.  When R is high, the drive runs at speed Sr1.

Note that the Preset Speed control feature is only active when the drive is in logic input control, CMOd=0, and in Remote mode.