Technical FAQs

Ask a Question

How long can the motor leads be on a ATV212 S-flex drive?

The longer the cable, the greater the capacitance. Cable lengths greater than 164 ft (50 m) may appear as a ground fault condition to the drive.  For installations where cable capacitances may be a problem, a reactor or motor protection filter can be installed between the drive and the motor.

The S-Flex is not intended to be used where extremely long output cable runs are required.  Maximum output cable length for standard duty motors should be limited to 100 m (328 ft).  For applications exceeding this cable length, consult the Drives PSG.  

CTA-ID : 2061718
Was this helpful?
What can we do to improve the information ?